  "version": "2.0.8",
  "blockingPrinciple": "A calculator is disabled where the controlling geometry or installation rule cannot be established from the supplied documents.",
  "items": [
    {
      "manufacturer": "Actionair",
      "family": "CSS",
      "issue": "The slab drawing combines an overall +10 to +30 mm opening with 5 to 20 mm edge clearances.",
      "decision": "Store overall oversize and per-edge constraints separately; do not assume central positioning."
    },
    {
      "manufacturer": "Actionair",
      "family": "DWFX-F",
      "issue": "Ordinary masonry pages do not publish a complete numerical opening rule.",
      "decision": "Keep those methods guidance-only unless the official drawing or hole-sizing logic is available."
    },
    {
      "manufacturer": "Lindab",
      "family": "WKS25",
      "issue": "Type A light-wall opening is +75 in the installation booklet and +70 in the short datasheet.",
      "decision": "Use +75 provisionally and show an audit warning."
    },
    {
      "manufacturer": "Advanced Air",
      "family": "26SCD",
      "issue": "Published tables are based on centralised installation but the detailed AFS constraints permit non-central positioning.",
      "decision": "Store table result and edge-limit logic separately; maximum case-to-edge clearance 130 mm, recommended batt space 25 mm."
    },
    {
      "manufacturer": "All",
      "family": "All",
      "issue": "Nominal duct and casing/frame dimensions are not interchangeable.",
      "decision": "Every setting-out calculation must identify its geometry reference explicitly."
    },
    {
      "manufacturer": "BSB",
      "family": "FSD-TD",
      "issue": "FSD-TD-C uses circular spigots on a rectangular multiblade casing, while FSD-TD-O lacks an explicit orderable flat-oval size/configuration table in the supplied series document.",
      "decision": "Enable FSD-TD-C only for the listed circular diameter table and calculate through the rectangular casing/method chain. Keep FSD-TD-O verification-required and do not extrapolate flat-oval configurations."
    },
    {
      "manufacturer": "BSB",
      "family": "FD Series Type C with Angle Frame",
      "issue": "The product code FD-C-AF can be confused with the separate FD-C Series circular single-blade damper. A site label confirms an FD-C-AF at Ø355.",
      "decision": "Create a distinct FD-C-AF product path. Apply the FD Series Type C circular-spigot and rectangular-casing geometry before the selected FD-AF method's 10 ±5 mm casing gap. Do not add Ø355 or Ø560 to FSD-TD-C."
    }
  ],
  "entries": [
    {
      "date": "2026-08-29",
      "manufacturer": "VentTools",
      "release": "V2.0.8-FD-USABILITY-AND-LINING-CONTROL",
      "summary": "Improved independent product identification, made the complete opening chain permanently visible and prevented alternative reveal-lining thicknesses from being presented as manufacturer-verified.",
      "controls": [
        "Original VentTools line diagrams are generic identification aids and are not manufacturer photographs or scale drawings",
        "Nominal duct, casing, finished aperture and structural cut remain visible without expanding a disclosure",
        "12.5 mm remains the recorded reference reveal lining where the selected mapped method includes one layer at each internal edge",
        "A 15 mm reveal-lining selection recalculates the structural cut but is explicitly marked review required",
        "Wall-face board layers remain separate from the aperture reveal-lining calculation"
      ]
    },
    {
      "date": "2026-08-29",
      "manufacturer": "VentTools",
      "release": "V2.0.7-PUBLIC-VERIFICATION",
      "summary": "Published the engineering verification method and author accountability as static public content while preserving the V2.0.6 calculation baseline.",
      "controls": [
        "The V2.0.6 bend take-off tables and common offset arithmetic remain unchanged",
        "A measured one-bend take-off can be entered for delivered fittings that differ from the recorded table",
        "Fire-damper calculation code and structured manufacturer rules remain unchanged",
        "Public guides distinguish nominal duct, casing, finished aperture, structural opening and reveal lining"
      ]
    },
    {
      "date": "2026-08-26",
      "manufacturer": "VentTools",
      "release": "V2.0.6-OFFSET-UX",
      "summary": "Improved the mobile offset-calculator controls and site wording without changing the calculation engine.",
      "controls": [
        "Straight-cut result is labelled as the cut straight between bends",
        "Standard circular duct sizes use a quick selector with a custom-size fallback",
        "Existing bend take-off tables, offset formulae and 120 mm editable swedge-limit warning are unchanged",
        "The fit warning is displayed immediately below the primary result"
      ]
    },
    {
      "date": "2026-08-21",
      "manufacturer": "BSB",
      "release": "V2.0.5-BSB-FD-C-AF",
      "summary": "Added the BSB FD Series FD-C-AF curtain-blade circular-spigot product as a separate calculator family, including verified Ø355 and Ø560 geometry.",
      "controls": [
        "FD-C-AF is not conflated with FD-C Series or FSD-TD-C",
        "Nominal diameter, D-3 spigot, rectangular casing, Angle Frame and aperture remain separate",
        "FD M9/M10/M11 retain the published 10 ±5 mm casing-gap tolerance"
      ]
    },
    {
      "date": "2026-08-21",
      "manufacturer": "BSB",
      "release": "V2.0.4-BSB-FSD-TD-FAMILY",
      "summary": "Added listed-diameter FSD-TD-C calculations, explicitly structured FSD-TD-S/C/O variants, and preserved nominal spigot to rectangular casing to clearance to structural opening geometry.",
      "controls": [
        "No opening calculated from circular spigot diameter alone",
        "No diameter extrapolation outside the FSD-TD-C table",
        "FSD-TD-O remains disabled pending an explicit size/configuration table"
      ]
    },
    {
      "date": "2026-07-19",
      "manufacturer": "Lindab",
      "release": "RC10-LINDAB",
      "summary": "Added method-specific builder setting-out mapping and Lindab engineering database for FNC1, WH25, WH45, WK25, WK45 and WKS25. FNC1U remains locked pending installation manual.",
      "controls": [
        "No invented casing projection",
        "Centred opening used only where shown/defined by tested opening detail",
        "Method-specific supports/fixings/separations retained"
      ]
    }
  ]
}